System graphic icons and labels that allow for simple, comprehensive generator set operation
Easy-to use 8” color LED touchscreen display features scroll navigation
Generator set and remote-mount options are available
Control Features
Island mode – single unit operation
High visibility graphical touchscreen display with alarm/event descriptions, set points, engine and generator monitoring
Intuitive navigation for display of power metering, protection, engine and generator parameters and tuning
Lockout security provision to assure platform integrity with three programable security levels
Support for 10 languages
Communications
Ethernet Modbus TCP for external communications
Support of up to four remote HMI’s (sold separately)
Compatible with Cat Connect Product Link devices
Embedded HMI Web Server
Advance Functionality
Automatic mains failure with utility voltage sensing capability (open transition) and remote breaker or contactor control/monitoring
Engine remote start integrity monitoring
Single genset transient load relief (TLR)
Advanced Overcurrent Protection
Arc Flash Maintenance Mode
Basic programmable logic control (PLC) function
EPA Tier 4 integration
Inducement override
Real (kW) load histograms
Status event log
Real-Time Clock
Programmable Cycle Timer (PCT)
Supports dynamic gas blending (DGB)
Applicable Standards and Certifications
Compliance with UL2200 3rd edition requirements including UL6200 functional safety requirements
Local annunciation facilitates compliance to NFPA 110 (subject to local authority having jurisdiction approval)
World Wide Product Support
Cat dealers have over 1,800 dealer branch stores operating in 200 countries
Your local Cat dealer provides extensive post-sale support, including maintenance and repair agreements
Data not available.
Standard Equipment
Control
Auto/Start/Stop
Emergency stop
Engine cooldown timer
Engine cycle crank
Programmable cycle timer
Speed and voltage adjust
Generator Monitoring
Generator AC voltage monitoring (+/- 0.25% accuracy)
Utility AC voltage monitoring (+/- 0.25% accuracy)
3 phase/4 wire (L-L & L-N) sensing
Generator current sensing (3 phase/6 wire) (+/- 0.25% accuracy)
Generator AC current (per phase and average)
Generator frequency
kWh, kVArh and import and export kVAh (total and trip)
Generator stator and bearing temperature (with optional RTD module)
kW load histogram
Generator Protection
Generator phase sequence (47G)
Over/Under voltage (27/59)
Over/Under frequency (81 O/U)
Overcurrent timed and inverse (50/51)
Overcurrent (thermal damage curve) (51)
Reverse power real (kW) (32)
Reverse power reactive (kVAr) (32RV)
Current balance (46)
Overload (49)
Engine Monitoring
Engine oil pressure (psi or kPa)
Engine oil temperature (°C or °F)
Engine coolant temperature (°C or °F)
Engine speed (RPM)
Battery voltage
Crank attempt and successful start counter
Run hour meter
Real time clock
Engine Protection
Control switch not in auto (alarm)
Low oil pressure
High coolant temperature (alarm and shutdown)
Low coolant temp (alarm)
Low coolant level (alarm and shutdown)
High engine oil temp (alarm and shutdown)
Low/High/Weak battery voltage
Fail to start
Overspeed
Overcrank
Low gas pressure (alarm and shutdown)
Communications
Primary and accessory CAN data link
Remote annunciator data link
Cat Data Link - with optional PLE702
Ethernet (Modbus TCP/IP) - 100 baseT
USB touchscreen display
4x 4-wire ports/managed switch (for internal and customer use)
2x 2-wire ports: internal device network
Inputs & Outputs
Digital Inputs: Emergency stop
Digital Inputs: Remote start
Digital Inputs: 16 programmable inputs (generator set configuration may affect available
features)
Digital Outputs: 12 programmable outputs (total)
Digital Outputs: Up to 2 programmable outputs for functional safety
Analog Outputs: 2 analog outputs
PWM Outputs: 3 total (1 for IVR - standard)
Analog Inputs: 3 programmable inputs 0-5V or resistive (generator set configuration
may affect available features)
Language Support
Multi-Language support
Environmental
Control Module Box
Operating Temp: -40°C to +85°C (Storage Temp: -55°C to +85°C)
Ingress Protection: IP66 (HMI Touchscreen from the front)
Optional Equipment
Display
Off-Package Remote HMI; The Cat ECS 100 supports up to four optional full function
remote HMI displays with the addition of an unmanaged Ethernet switch. The interactive
color touchscreen graphical interface serves to display generator set system alarm
conditions, status indications and annunciation facilitates compliance to NFPA110
(subject to local authority having jurisdiction approval)
RS-485 Annunciator
The remote RS-485 annunciator serves to display genset system alarm conditions and
status indications for 16 points with a standard NFPA 99 and 110 label. The annunciator
has been designed for use on the long-distance annunciator datalink and may be used
in remote (up to 4000 feet) applications.
A maximum of four annunciators may be used with a Cat ECS 100.
Digital Input/Output Module
The digital input/output (DI/O) module serves to provide expandable input and output
for any event and is capable of reading 12 discrete inputs and setting 8 relay outputs.
The DI/O module has been designed for use on the accessory communication network and
may be used in either local (package mounted) or remote (up to 244 meters or 800 feet)
applications.
A maximum of four DI/O modules may be used with a Cat ECS 100.
RTD Module
The RTD module serves to provide expandable generator set temperature monitoring capability
of the Cat ECS 100 control system and is capable of reading up to eight type 2-wire,
3-wire and 4-wire RTD inputs. The RTD Module has been designed for use on the Accessory
Communication Network and may be used in either local (package mounted) or remote
(up to 244 meters or 800 feet) application.
A maximum of one RTD Module may be used with a Cat ECS 100.
Communications
Expansion Input/Output Ethernet Modules
- Supports expanded Inputs/Outputs (IO) capability of the Cat ECS 100 control: Analog
and digital I/O and Temperature sensing (RTD)
- Configure I/O for any event (read and write function)
- Package mounted and/or ship loose options
Related Products
Units:
Diesel Generator Sets
Cat diesel generator sets rated 6 to 5,720 ekW (7.5 to 7,150 kVA) for standby or prime power provide efficiency, low fuel consumption and emissions compliance. Our commercial and industrial generator sets come prepared for emergency duty or to meet on-going needs.
Cat industrial and commercial gas generator sets, at ratings from 100 to 4,500 ekW (100 to 4,500 kVA), operate on natural gas and a wide range of other gaseous fuels including biogas, landfill gas, coal gas and propane..