The ATC-900 C9ontroller is a programmable microprocessor-based monitoring device for use on Cat transfer switches. Data access and programming operations are performed using the ATC-900's touch sensitive function buttons in conjunction with an easy-to-read illuminated alphanumeric LED display. Both the functional buttons and the display window are part of the device's door mounted front panel. A built in Help button provides user assistance in the form of message displays.
The communication option permits monitoring and control of several transfer switches, locally or remotely from a single point. Depending on the application, the user can customize the ATC-800 to meet the particular application. The ATC-900 is equipped to display historical information either via the front panel or over mod bus communications to a personal computer. Source 1 and Source 2 run time, available time and connect time are available, as well as load energized time, number of transfers, date, time and reason for the last 16 transfers.
Rating Range | 120 to 600V, single phase and three phase @ 50/60 Hz |
Transfer Type | Switch application dependent |
Switch Type | Switch application dependent |
Factory programming will load all standard features and customer-specified options per the default settings.
Rating Range | 120 to 600V, single phase and three phase @ 50/60 Hz |
Transfer Type | Switch application dependent |
Switch Type | Switch application dependent |
Input Control Voltage | 120Vac (50/60 Hz) (operating range 65 to 160 Vac) |
Voltage Measurements of Utility | Source 1, Source 2 and Load<br>(VAB, VBC, VCA for Three Phase System) |
Voltage Measurement Range | 0 to 700 Vac |
Voltage Measurement Accuracy | +/-1% of full scale |
Frequency Measurements Of | Source 1 and Source 2 |
Frequency Measurement Range | 40 Hz to 80 Hz |
Frequency Measurement Accuracy | +/- 0.1 Hz |
Undervoltage Dropout | Breaker Style 50 to 97% of Nominal System Voltage<br>Contactor Style - 78 to 97% |
Undervoltage Pickup | (Dropout +2%) to 99% of Nominal System Voltage |
Underfrequency Dropout Range | 90 to 97% of Nominal System Frequency |
Underfrequency Pickup Range | (Dropout +1 Hz) to 99% of Nominal System Frequency |
Overfrequency Dropout Range | 103 to 110% of Nominal System Frequency |
Overfrequency Pickup Range | 101% to (Dropout +1 Hz) of nominal system frequency |
Operating Temperature Range | -20 to 70 degree C (-4 to +158 degree F) |
Operating Humidity | Up to 90% Relative Humidity (non-condensing) |
Enclosure Compatibility | <li>NEMA 12 (std mounting)</li><lNEMA 4/4X</li><li>NEMA 3R</li><li>UV Resistant Faceplate</li> |
System Voltage Application | 120 to 600 Vac (50/60 Hz) (single or three phase) |
Factory programming will load all standard features and customer-specified options per the default settings.
In-phase monitor is a feature that will allow a transfer between two sources only when the phase difference between the two sources is near zero. This is an open transition transfer that prevents in-rush currents from exceeding normal starting currents in the case where motor loads are being transferred.
Load voltage decay transfer is a feature that, after opening the switch for the original source, holds in the neutral position until the voltage on the load is less than 30% of rated voltage. This operation is an open transition that prevents in-rush currents from exceeding normal starting currents in the case where motor loads are being transferred.