/  Power Systems  /  Electric Power  /  ATS MX Contactor

CTX Series Automatic Transfer Switch

CTX Series Automatic Transfer Switch

Overview


Cat® CTX Series switches are built for residential and light commercial applications requiring the dependability and ease of operation found in a power contactor switch.

Voltage sensing and system control is performed via a state-of-the-art microcontroller located on the cabinet door.

Specifications

Units: 
Rating Range 40-400A
Transfer Type Open transition
Switch Type Contactor Based
See more

Benefits & Features

MX Control Panel

      CTX switches are equipped with the MX-60 control panel as standard.
      This microprocessor control includes:
    • Undervoltage sensing (90% pickup/80% dropout of the utility source
      • Voltage and frequency sensing of the generator source (90% voltage/95% frequency pickup)
      • Time Delay Engine Start – 5 seconds (P)
      • Time Delay Engine Warmup – Transfer to Generator – 20 seconds (W)
      • Time Delay Utility Stabilization/Retransfer to Utility – 5 minutes (T)
      • Time Delay Engine Cool Down – 5 minutes (U)

      All time delays are fixed.

  March 27, 2024

Specifications

Units: 
Technical Summary
Rating Range 40-400A
Transfer Type Open transition
Switch Type Contactor Based

Benefits & Features

MX Control Panel

      CTX switches are equipped with the MX-60 control panel as standard.
      This microprocessor control includes:
    • Undervoltage sensing (90% pickup/80% dropout of the utility source
      • Voltage and frequency sensing of the generator source (90% voltage/95% frequency pickup)
      • Time Delay Engine Start – 5 seconds (P)
      • Time Delay Engine Warmup – Transfer to Generator – 20 seconds (W)
      • Time Delay Utility Stabilization/Retransfer to Utility – 5 minutes (T)
      • Time Delay Engine Cool Down – 5 minutes (U)

      All time delays are fixed.

Standard Equipment

  • The unit is available in open type, NEMA 1 or NEMA 3R enclosures. The MX-60 control panel adds a user interface and functionality, including:
    • Pushbuttons for test, exercise set, timer bypass and program cancel
    • Special status annunciation of in-phase transfer and times operation
    • Diagnostic LED indications in logical one-line configuration
    • Selectable 7, 14, 21 or 28 day (factory set 28 days) generator exerciser timer
    • Indicating LEDs for power availability, switch position and load energized
  • Additional options include:
    • A3/A4 Auxiliary contacts (1 each) closed in utility and generator positions
    • Special timer settings

View 360