C15 (60 Hz) Tier 4 InterimNon-Current

C15 Tier 4 Interim (60)

Specifications

Units: 
Minimum Rating 455 ekW
Maximum Rating 500 ekW
Emissions/Fuel Strategy EPA Tier 4 Interim
See more

Benefits & Features

Generator

EMCP Control Panel

World Wide Product Support

  October 31, 2024

Specifications

Units: 
Generator Set Specifications
Minimum Rating 455 ekW
Maximum Rating 500 ekW
Emissions/Fuel Strategy EPA Tier 4 Interim
Voltage 208 to 600 Volts
Frequency 60 Hz
Speed 1800 RPM
Engine Specifications
Engine Model C15 ATAAC, I-6, 4-Stroke Water-Cooled Diesel
Compression Ratio 16.1:1
Aspiration Air to Air Aftercooled
Governor Type Adem™A4
Fuel System MEUI
Bore
Displacement
Stroke

Benefits & Features

Generator

Generator

  • Matched to the performance and output characteristics of Cat engines
  • Industry leading mechanical and electrical design
  • Industry leading motor starting capabilities
  • High Efficiency

EMCP Control Panel

EMCP Control Panel

The EMCP controller features the reliability and durability you have come to expect from your Cat equipment. EMCP4 is a scalable control platform designed to ensure reliable generator set operation, providing extensive information about power output and engine operation. EMCP4 systems can be further customized to meet your needs through programming and expansion modules.

World Wide Product Support

World Wide Product Support

Cat dealers provide extensive post-sale support including maintenance and repair agreements. Cat dealers have over 1,800 dealer branch stores operating in 200 countries. The Caterpillar S•O•S℠ program cost effectively detects internal engine component condition, even the presence of unwanted fluids and combustion by-products

Standard Equipment

  • Air Inlet
    • Air cleaner
  • Cooling
    • Package mounted radiator
  • Exhaust
    • Exhaust flange outlet
  • Fuel
    • Secondary fuel filters
    • Fuel priming pump
    • Primary fuel filter with integral water separator
  • Generator
    • Matched to the performance and output characteristics of Cat engines
    • Load adjustment module provides engine relief upon load impact and improves load acceptance and recovery time
    • IP23 Protection
  • Power Termination
    • Busbar
  • Control Panel
    • EMCP 4 Genset controller
  • Mounting
    • Rubber vibration isolators
  • Starting/Charging
    • 24 volt starting motor
    • Batteries
  • General
    • Paint - Caterpillar yellow except rails and radiators gloss black

Optional Equipment

  • Exhaust
    • Industrial, residential, critical mufflers
  • Generator
    • Permanent magnet excitation (PMG)
    • Anti-condensation heater
    • Internal excitation (IE)
    • Oversize and premium generators
  • Power Termination
    • Circuit breakers, UL listed
    • Circuit breakers, IEC compliant
  • Control Panels
    • EMCP 4.4
    • Local & remote annunciator modules
    • Load share module
    • Digital I/O module
    • Remote monitoring software
  • Starting/Charging
    • Battery chargers
    • Oversize batteries
    • Jacket water heater
    • Heavy duty starting system
    • Charging alternator
  • General
    • The following options are based on regional and product configuration:
    • Seismic Certification per applicable building codes: IBC 2000, IBC 2003, IBC 2006, IBC 2009, CBC 2007
    • UL 2200 package
    • EU Certificate of Conformance (CE)
    • CSA Certification
    • EEC Declaration of Conformity
    • Narrow, wide or skid base
    • Sound attenuated, weather protective or high ambient weather protective enclosure
    • Single or dual wall integral fuel tanks
    • Single or dual wall sub-base fuel tanks
    • Integral & sub-base UL listed dual wall fuel tanks
    • Automatic transfer switches (ATS)

View 360