C7.1 Tier 4 (60 Hz)Non-Current

C7.1 T4 (US Source) (60)

Overview

Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.

Specifications

Units: 
Minimum Rating 114 ekW
Maximum Rating 200 ekW
Emissions/Fuel Strategy U.S. EPA Cert,. Tier 3
See more

Benefits & Features

Design Criteria

    • The generator set is designed to meet ISO8528-5 transient response and NFPA 110.
    • Cooling system designed to operate in 50˚C / 122˚F ambient temperatures with an air flow restriction of 0.5 in. water

Cat Diesel Engine

    • Reliable, rugged, durable design
    • Field-proven in thousands of applications worldwide
    • Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight

Generator

    • Matched to the performance and output characteristics of Cat engines
    • Industry leading mechanical and electrical design
    • Industry leading motor starting capabilities
    • IP 23 Protection

  April 6, 2024

Specifications

Units: 
Generator Set Specifications
Minimum Rating 114 ekW
Maximum Rating 200 ekW
Emissions/Fuel Strategy U.S. EPA Cert,. Tier 3
Voltage 208 to 480 Volts
Frequency 60 Hz
Speed 1800 rpm
Engine Specifications
Engine Model C7.1 I-6, 4-Cycle Diesel
Displacement
Fuel System Common Rail
Aspiration Turbocharged, Air to Air Aftercooled
Governor Type ADEM™A4
Compression Ratio 16.5:1
Bore
Stroke
Generator Set Dimensions
Length - Maximum
Width - Maximum
Height - Maximum

Benefits & Features

Design Criteria

    • The generator set is designed to meet ISO8528-5 transient response and NFPA 110.
    • Cooling system designed to operate in 50˚C / 122˚F ambient temperatures with an air flow restriction of 0.5 in. water

Cat Diesel Engine

    • Reliable, rugged, durable design
    • Field-proven in thousands of applications worldwide
    • Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight

Generator

    • Matched to the performance and output characteristics of Cat engines
    • Industry leading mechanical and electrical design
    • Industry leading motor starting capabilities
    • IP 23 Protection

EMCP Control Panel

The EMCP controller features the reliability and durability you have come to expect from your Cat equipment. The EMCP 4 is a scalable control platform designed to ensure reliable generator set operation, providing extensive information about power output and engine operation. EMCP 4 systems can be further customized to meet your needs through programming and expansion modules. The EMCP4.1 is fitted as standard

World Wide Product Support

Cat dealers provide extensive post-sale support including maintenance and repair agreements. Cat dealers have over 1,800 dealer branch stores operating in 200 countries. The Caterpillar S•O•S℠ program cost effectively detects internal engine component condition, even the presence of unwanted fluids and combustion by-products

Single-Source Supplier

Fully prototype tested with certified torsional vibration analysis available

CE Certification

CE Certification available

General

    • Single wall 8 hour wide fuel tank
    • Circuit breaker, IEC, 3 pole
    • Industrial Silencer (10 dBA)

Standard Equipment

  • Air Inlet System
    • Air cleaner; light duty with disposable element
  • Control Panels
    • EMCP 4.1
  • Cooling System
    • Fan drive, battery charging alternator drive
    • Radiator and cooling fan with guards
    • Caterpillar extended life coolant
    • Coolant drain line with valves
  • Exhaust System
    • Stub pipe, gaskets, raincap and SAE exhaust flange for customer use - shipped loose
  • Fuel System
    • Standard open set fuel tank/base supplied
    • Base, formed steel with single wall integral 8-hour fuel tank
  • Generator and Generator Attachments
    • Voltage regulator (single phase sensing)
    • 12 Leads
    • IP23 Protection
    • Circuit breaker, IEC, 3 pole, mounted in tower panel
    • Segregated low voltage (AC/DC) wiring panel
    • Tower panel, IP22, bottom cable entry
  • Starting / Charging System
    • 24V battery with rack and cables
  • Governing System
    • Mechanical and electrical governing system - model dependent
  • Lube System
    • Lubricating oil
    • Oil drain line with valve
  • Mounting System
    • Includes lifting provision and drag points
    • Captive linear vibration isolators between base and engine-generator
    • Termination points for coolant and lube oil drain lines
  • General
    • Engine and alternator pre-paint, Caterpillar yellow

Optional Equipment

  • Alternator System
    • Anti-condensation heater
    • 3 Phase sensing
    • Alternator removal
    • Optional LC Frame alternator
    • Quatrature droop king
    • R Frame auxiliary winding: R2273L4 SE aux alt 07, aux alt 08 and aux alt 10
    • Optional LC Frame alternator with coastal insulation protection
    • Permanent magnet excitation (PMG)
  • Circuit breakers
    • 4 Pole 250A, 400A and 630A Circuit breakers
    • Padlockable breaker device
  • Control Panel Options
    • Earth fault (2 wire only)
    • Control panel heater
    • Battery charger
    • Earth leakage (2 wire only)
    • Speed adjust contacts
    • Volt free contacts
    • Overload shutdown via breaker
    • Emergency stop with key
    • Speed adjust potentiometer
    • Panel mounted audible alarm
  • Cooling System
    • Low coolant level shutdown
    • Coolant heater
    • Low coolant temperature
  • Control System
    • Volt free contacts for generator set running
    • Volt free contacts for common alarm
    • EMCP 4.2
    • Static battery charger
    • Control panel heater
  • Enclosures
    • Rental options (CAE only) - Socket blanking plate
    • Rental options (CAE only) - Single point lift
    • Rental options (CAE only) - Rental pack
    • Rental options (CAE only) - CEE form sockets for enclosure
    • Sound attenuated levels 1 and 2 enclosures
  • European Certifications
    • Upgrade to STD set for CE
  • Fuel Systems
    • Compact skidbase for open sets
    • Low fuel level alarm
    • DEFRA bunded fuel tank
    • Low fuel level shutdown
    • Open set narrow tankbase
    • Skidbase for CALG enclosure sets
    • High fuel level alarm
  • Mounting Options
    • Industrial silencer removal
    • Silencer installation kit
    • Electronic governor
    • Residential silencer
    • Battery removal
  • Test Reports
    • PGS Test report @ 1.0 power factor
    • PGS Test report @ 0.8 power factor
  • General
    • Stone guards/radiator trans flange
  • Global Certifications
    • Certification for CIS
  • Power Termination
    • Circuit breaker, IEC, 4 pole
  • Accessories / Miscellaneous
    • Packing case - canopied set
    • Packing case - compact set

View 360