Caterpillar offers a range of integrated switchgear solutions, from standard floor standing low voltage ACB's breakers 1600A - 4000A to custom solutions, which can include multiple utility sources with multiple generator paralleling applications where complex control philosophies are employed. Caterpillar has developed a modular low voltage switchgear enclosure range which integrates controls and PLC solutions. Built around 150mm modules in 3 axis, internally the framework utilises a 25 mm grid allowing a fully configurable system. Enclosure options include form 4 separation, IP54 protection and 50 °C capabilities.
Configuration | IP4X |
Operating Temperature | 35 °C / 40 °C @ 1 hr, option for 0…50 °C (32…122 °F) |
Standard Widths | 600 mm for ABB Emax2 E2 1600 - 2500A. 750 mm for ABB Emax2 E4 3200 - 4000A. 1200 mm for ABB Emax2 E6 4000 - 6300A. |
Configuration | IP4X |
Operating Temperature | 35 °C / 40 °C @ 1 hr, option for 0…50 °C (32…122 °F) |
Standard Widths | 600 mm for ABB Emax2 E2 1600 - 2500A. 750 mm for ABB Emax2 E4 3200 - 4000A. 1200 mm for ABB Emax2 E6 4000 - 6300A. |
Standard Heights | Heights include 100mm plinth with fork lift pockets, 1900 mm up to 3200A, 2200 mm for 400,2200 mm for PLC and control cabinets. Option for single point lifting on 4 corners with M10 swivel eyes. Standard sizes for shipping |
Standard Depths | 300, 450 & 750mm for controls and PLC cabinets. 900mm for fixed breakers. 1050mm for withdrawable breakers |
Technical Summary | Modular system enables any configuration Distribution Boards, Motor Control Centers & PLC Control cabinets. Accommodates fixed or withdrawable breakers. |
Application | LV 380…480 VAC, 50 Hz, 3-Phase. |
Modes of Operation | Switchgear integration options for multi generator and utility synchronising, load sharing, Peak Lopping/Shaving, AMF, Changeover, Load bank connection, Protection relay etc. |
Data not available.