Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.
Governor Type | ADEM™A4 |
Weight | 32470 kg / 71,584 lbs |
Generator Excitation | Internal Excitation |
EU Certificate of Conformance 2006/42/EC Machinery Directive (MD) 2006/95/EC Low Voltage Directive (LV) 89/336/EEC EMC Directive EN 12601 Reciprocating internal combustion engine driven generating sets EN 61439 Low voltage switchgear and control gear assemblies EN 62040-1 Uninterruptible Power Systems (UPS) – General and safety requirements for UPS EN 60204 Safety of machinery – Electrical equipment of machines 2000/14/EC Noise emission by outdoor
Governor Type | ADEM™A4 |
Generator Excitation | Internal Excitation |
Fuel System | Electronic Unit Injection |
Displacement | — |
Generator Voltage Regulator | 3 Phase Sensing |
Generator Frame Size | 1445 |
Generator Voltage Regulation | Less than +/- 0.5% (steady state), Less than +/- 1% (no load to full load), |
Electrical Power Output | 1400 kVA Standby |
Engine Model | 3512B TA, V-12, 4-stroke water-cooled diesel |
Model | Cat C3512B |
Weight | 32470 kg / 71,584 lbs |
Voltage | 480 VAC 3-Phase, 3 wire plus ground |
Dimensions (ISO 20 ft High Cube) | 12,192 x 2,438 x 2,896 mm / 480 x 96 x 114 in |
Noise Level - Generator Online | 85 dBA@1m |
Frequency | 60 Hz +/- 10% max (programmable) |
Continuous Power Output | 1200 kVA (960 kW @ PF 0.9) |
Flywheel Type | 1200Z SeriesMultile Module System (MMS) |
Maximum kW / (kVA) | 960 (1200) |
Certifications | UL 1778 listed, EN5009-1-1, CUL CAN/CSA 22.2 No. 107.1 listed, CE Mark |
AC Output Current at 480 VAC (amps) | 1445 |
AC Output Voltage | 480 VAC 3‐Phase, 3 wire plus ground |
Input Voltage | 400 VAC 3‐Phase, 3 wire plus ground |
Maximum Continuous Input | 1600 |
AC Output Frequency | 60 Hz (mains synchronized) normal operation +/- 2% free running |
Input Voltage Range | +10% / ‐15% (programmable) |
EU Certificate of Conformance 2006/42/EC Machinery Directive (MD) 2006/95/EC Low Voltage Directive (LV) 89/336/EEC EMC Directive EN 12601 Reciprocating internal combustion engine driven generating sets EN 61439 Low voltage switchgear and control gear assemblies EN 62040-1 Uninterruptible Power Systems (UPS) – General and safety requirements for UPS EN 60204 Safety of machinery – Electrical equipment of machines 2000/14/EC Noise emission by outdoor
Cat Dealers provide extensive post sale support including maintenance and repair agreements. One single service contract for the complete Cat CPM Cat dealers have over 1,800 dealer branch stores operating in 200 countries. The Cat S•O•SSM program cost effectively detects internal engine component condition, even the presence of unwanted fluids and combustion by-products
By cancelling harmonic distortion, the UPS operates seamlessly with the generator set to provide a higher total electrical load capacity without oversizing the generator set. Cat UPS effectively insulates the generator set from block loads and transient, and can improve its fault clearing capabilities. The CPM is factory tested and all programmable integration parameters adjusted at factory that assures greater system reliability and improves the total system operation.
Caterpillar's high operating efficiency (>97%) means yearly savings versus traditional battery UPS products. In addition, lower Cat UPS heat rejection reduces up front HVAC costs and electrical consumption over the life of the product.
Superior system design and the use of robust digital components throughout the system yield the most reliable and trouble-free UPS system on the market. Protection is delivered in the industry's smallest package with the highest efficiency and superior performance.
A 4-pole, Open Transition Automatic Transfer Switch will switch the load between the utility source and the generator. It is fully rated to the generator output and incorporates convenient customer connections for Continuous and Non-critical load. Connection points are also available for load bank testing or a rental generator set.
Data not available.