Various applications are available such as Multiple Generator Control, Multiple Utility control (including Peak Lopping/Shaving), Load Management control and Balance of Plant control. At a basic level, a Master PLC panel is wired in conjunction with the generator control panels and associated switchgear in the system to provide the control for the power network and the starting and stopping of the generators. For more complex systems, a communication network can be utilised to facilitate the transfer of data between the PLC and outstations from different locations. The network comprises physical connections between all intelligent devices (or nodes) arranged into a ring formation and operating on the EtherNet/IP protocol.

Specifications

Units: 
Configuration IP4X
Operating Temperature 0 - 50 °C (32 - 122 °F)
Dimensions Depth 750 mm, Width 750 mm, Height 2200 mm
See more

Benefits & Features

PLC and SCADA Control Systems

    • Auto/Manual control of generators and load breakers
    •     Generator monitoring screens (Voltage, Frequency, Amps, kW, kVA, kVAr)
    • Engine monitoring screens (Oil pressure, Engine temperature, RPM, Engine hours, Battery DC Voltage, Number of starts)
    • Generator test off load buttons
    • Test buttons for Utility synchronising
    • Generator and breaker alarm and event logging
    • Suitable for complex control philosophies using standard add-on instructions within a configurable base code
    • Modular system, can be scaled to suit any application
    • Simple interface with Modbus (RS485, Ethernet), BacNet and Profibus systems
    • Remote Access, monitoring and control

  April 5, 2024

Specifications

Units: 
Enclosure Rating
Configuration IP4X
Operating Temperature
Operating Temperature 0 - 50 °C (32 - 122 °F)
Dimensions
Dimensions Depth 750 mm, Width 750 mm, Height 2200 mm
Application
Application LV and MV
Modes of Operation
Modes of Operation AMF control, Multiple Generator control, Multiple Generator Group control, Multiple Utility control, Baseload control, Import/Export control, Load Management control, Balance of Plant control
Technical Summary
Technical Summary Customisable PLC and SCADA in a floor standing control panel.

Benefits & Features

PLC and SCADA Control Systems

    • Auto/Manual control of generators and load breakers
    •     Generator monitoring screens (Voltage, Frequency, Amps, kW, kVA, kVAr)
    • Engine monitoring screens (Oil pressure, Engine temperature, RPM, Engine hours, Battery DC Voltage, Number of starts)
    • Generator test off load buttons
    • Test buttons for Utility synchronising
    • Generator and breaker alarm and event logging
    • Suitable for complex control philosophies using standard add-on instructions within a configurable base code
    • Modular system, can be scaled to suit any application
    • Simple interface with Modbus (RS485, Ethernet), BacNet and Profibus systems
    • Remote Access, monitoring and control

Standard Equipment

  • 17 inch Industrial Computer with touchscreen graphical Interface
    • Project specific screens
    • Single Interface for monitoring and control
    • Data logging
    • Alarm/Event logging
    • Password protection for control

Optional Equipment

  • Redundant Hot/Standby PLC's
    • Dimensions 2200 (H), 2250mm (W), 750mm (D)
    • Each PLC is installed in a separate panel with all interconnecting cables connected to a marshalling section.
  • High speed Ethernet Ring network for connection to remote outstations
    • A Ring network is a single-fault tolerant network, providing fast recovery time when a single fault occurs on the network.