CPM1000Non-Current

CPM1000

Overview

Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.

Specifications

Units: 
Electrical Power Output 1250 kVA Standby
Displacement
AC Output Current VAC (amps) 380 (1521), 400 (1445), 415 (1393)
See more

Benefits & Features

Cat Diesel Engine

  • Reliable, rugged, durable design
  • Field-proven in thousands of applications worldwide
  • Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight

Generator

  • Matched to the performance and output characteristics of Cat engines
  • Industry leading mechanical and electrical design
  • Industry leading motor starting capabilities
  • IP 23 Protection

Certification and Standards

 EU Certificate of Conformance  2006/42/EC Machinery Directive (MD)  2006/95/EC Low Voltage Directive (LV)  89/336/EEC EMC Directive  EN 12601 Reciprocating internal combustion engine driven generating sets  EN 61439 Low voltage switchgear and control gear assemblies  EN 62040-1 Uninterruptible Power Systems (UPS) – General and safety requirements for UPS  EN 60204 Safety of machinery – Electrical equipment of machines  2000/14/EC Noise emission by outdoor

  April 5, 2024

Specifications

Units: 
Generator Set Specifications
Electrical Power Output 1250 kVA Standby
Displacement
Model Cat C32
Generator Voltage Regulation Less than +/- 0.5% (steady state), Less than +/- 0.5% (3% speed change)
Engine Model C32 ATAAC, V-12 4-stroke water-cooled diesel
Governor Type ADEM™A4
Generator Excitation Internal Excitation
Fuel System MEUI™
Generator Voltage Regulator 3 Phase Sensing
Generator Frame Size 1424
UPS Specifications
AC Output Current VAC (amps) 380 (1521), 400 (1445), 415 (1393)
Maximum kVA / (kW) 1000 (900)
AC Output Frequency 50 Hz (mains synchronized) normal operation =/- 10% input
Certifications EN59001‐1-1
AC Output Voltage 380/400/415 VAC 3‐Phase, 4 wire plus ground
Input Voltage 380/400/415 VAC 3‐Phase, 4 wire plus ground
Maximum Continuous Input 1600 amps
Input Voltage Range +10% / ‐15% (programmable), +/‐10% at 380 VAC
CPM1000 Specifications
Noise Level - Generator Online 85 dBA@1m
Weight 27765 kg / 61212 lbs
Dimensions (ISO 20 ft High Cube) 12,192 x 2,438 x 2,896 mm / 480 x 96 x 114 in
Frequency 50 Hz +/- 10% max (programmable)
Voltage 380/400/415 VAC 3-Phase, 4 wire plus ground
Continuous Power Output 1000 kVA (900 kW @ PF 0.9)
1000iZ Series Multiple Module System (MMS)
Flywheel Type 300 Series Single Module System (SMS)

Benefits & Features

Cat Diesel Engine

  • Reliable, rugged, durable design
  • Field-proven in thousands of applications worldwide
  • Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight

Generator

  • Matched to the performance and output characteristics of Cat engines
  • Industry leading mechanical and electrical design
  • Industry leading motor starting capabilities
  • IP 23 Protection

Certification and Standards

 EU Certificate of Conformance  2006/42/EC Machinery Directive (MD)  2006/95/EC Low Voltage Directive (LV)  89/336/EEC EMC Directive  EN 12601 Reciprocating internal combustion engine driven generating sets  EN 61439 Low voltage switchgear and control gear assemblies  EN 62040-1 Uninterruptible Power Systems (UPS) – General and safety requirements for UPS  EN 60204 Safety of machinery – Electrical equipment of machines  2000/14/EC Noise emission by outdoor

World Wide Product Support

 Cat Dealers provide extensive post sale support including maintenance and repair agreements.  One single service contract for the complete Cat CPM  Cat dealers have over 1,800 dealer branch stores operating in 200 countries.  The Cat S•O•SSM program cost effectively detects internal engine component condition, even the presence of unwanted fluids and combustion by-products

UPS Generator Set Integration

By cancelling harmonic distortion, the UPS operates seamlessly with the generator set to provide a higher total electrical load capacity without oversizing the generator set. Cat UPS effectively insulates the generator set from block loads and transient, and can improve its fault clearing capabilities. The CPM is factory tested and all programmable integration parameters adjusted at factory that assures greater system reliability and improves the total system operation.

UPS Lower Operating Cost

Caterpillar's high operating efficiency (>97%) means yearly savings versus traditional battery UPS products. In addition, lower Cat UPS heat rejection reduces up front HVAC costs and electrical consumption over the life of the product.

UPS Superior Design

Superior system design and the use of robust digital components throughout the system yield the most reliable and trouble-free UPS system on the market. Protection is delivered in the industry's smallest package with the highest efficiency and superior performance.

Automatic Transfer Switch

A 4-pole, Open Transition Automatic Transfer Switch will switch the load between the utility source and the generator. It is fully rated to the generator output and incorporates convenient customer connections for Continuous and Non-critical load. Connection points are also available for load bank testing or a rental generator set.

Standard Equipment

  • Flywheel Energy Storage
    • Compact, battery free, low cost maintenance / operation
  • Starting System
    • GenStart module provides up to 1725 cold cranking amps @ 24 VDC and is redundant to the generator set starting batteries for highest system reliability. Battery charger integrated.
  • Control system
    • LCD monitor/control HMI panel installed on UPS/ATS/Generator set. Monitoring and alarms for critical components with self-diagnostics. Two (2) warning tower lights installed on exterior of container.
  • Communication with Integrated System
    • Integral modem for remote communication. MODBUS (RTU or TCP/IP). Remote notification and monitoring via Ethernet and e-mail. RS232 or RS485 serial connection. Real-time monitoring software available (UPS View / EMCP Monitoring Software).
  • Cooling System
    • Louvers installed on input and output of the container. Redundant cooling fans on UPS with speed regulation by temperature control unit.
  • Engine Coolant System
    • Jacket water heater. Coolant level sight gauge.
  • Switchgear Integration
    • Automatic Transfer Switch (ATS) – controlled by microprocessor-based unit. Integrated maintenance bypass. Convenient customer connection for continuous load and non-critical load output. Fuel System Integrated fuel system with fuel tank, primary fuel filter with integral water separator,
  • Fuel System
    • Integrated fuel system with fuel tank, primary fuel filter with integral water separator, secondary fuel filters and fuel priming pump.

View 360